En caso de detectar un código que no esté en la lista, póngase en contacto con el servicio de
asistencia técnica de Samsung.
© Intesis Software SLU - Todos los derechos reservados
Esta información puede cambiar sin previo aviso
®
IntesisBox
es una marca registrada de Intesis Software SLU
SM-RC-MBS-1
Configuration error
Communication error
Communication error
Communication error
Installation error
Configuration error
Configuration error
Configuration error
Configuration error
Configuration error
Configuration error
Configuration error
Configuration error
SM-RC-MBS-1
Option Code Miss match indoor units
Communication error between wired remote and
indoor unit. (When communication has stopped
for 3 minutes after detecting indoor unit and
wired remote control)
Communication error between the Master and
Slave wired remote controller. (Only one Master
and one Slave can exist).
Tracking 10 or more errors between wired
remote control and indoor unit.
-COM1, Com2 crossing connection error.
-When wired remote is connected to indoor unit
COM1 (F1, F2) terminals.
-Multiple Master error. (When using Master
remote control).
-Error occurs when two wired remotes are both
set as Master in one COM line.
Indoor unit is not installed. (when the indoor
unit is not detected after outside gearing option
setting and tracking are finished). In case of
using outside gear control.
-Exceeded maximum no. of installation for
indoor units.
-A reset is required after checking the number
of indoor unit.
-Mixed installations for °C/F° indoor unit. (Only
detected on master wired remote control).
-Error occurs when mixed indoor units of °C and
°F settings are installed.
-Wired remote control °C/°F setting error.
-This error occurs if the indoor unit is set in °C
while the wired remote is set in °F or vice versa.
This error occurs when the option setting of the
Master and Slave wired remote controls are
different from each other.
Slave wired remote control installation error
(when two Slave wired remote controls are
installed).
Wired remote controller COM2 option setting
error.
Error in the communication of SM-RC-MBS-1 or
Remote Controller with the AC unit.