Diffuser Probe

Step 1: Remove sensing port caps.
Step 2: Connect two hoses (C) to sensing ports (B).
E Diffuser
Probe
Step 3: Select proper Range Selector (D).
Note: For velocities below 2500 feet per minute, use the Range Selector
with black letters; for velocities above 2500 feet per minute, use the
Range Selector with red letters.
Step 4: Connect Range Selector (D) to loose ends of hoses (C) that are
already connected to the meter (A) as follows:
D Range
Selector
Da Switch
Button
Db Switch
Plate
Step 5: Insert Diffuser Probe (E) into the Range Selector (D). Push the
Diffuser Probe firmly down until the collar of the probe rests against the
C Hose
top of the Range Selector.
Step 6: Check position of switch button (Da) on Range Selector (D). It
B Sensing
must be pushed in and turned to latch it in.
Ports
Step 7: Check position of switch plate (Db) on Range Selector (D). It
must be positioned for the proper velocity range.
Step 8: Proceed to make necessary velocity measurements; see page 11
for procedures.
A Meter

PREPARATION FOR USE

For Supply Measurements

Connect the plus (+) sensing port of the meter to the plus (+) sensing
port of the Range Selector, and the minus (–) sensing port of the
meter to the minus (–) sensing port of the Range Selector.

For Return and Exhaust Measurements

Connect the plus (+) sensing port of the meter to the minus (–)
sensing port of the Range Selector, and the minus (–) sensing port of
the meter to the plus (+) sensing port of the Range Selector.
7