DETAILED DESCRIPTION OF OBJECTS

Common to all objects

When the indoor unit is communicating normally, communication can be established between
the Aidoo Pro and the indoor unit. The BACnet Building Management System (BMS) will have
access to the Airzone AC unit objects.
If communication between Aidoo Pro and the system is not successful, or if the request for
information related to the communication object is not found within the Airzone system, the
object property "out of service" is activated.

Switching On/Off

Aidoo Pro will communicate the status of each specific zone. Through the BACnet platform,
any zone can be configured as on/off. These are read/write objects.

IU communication

If the indoor unit loses communication, Aidoo Pro will communicate this to BACnet. This object
is read only.
Read (R) / Write
(W)
0
R/W
0
R
1
R
2
R
0
R
0
R/W
1
R
0
R/W
1
R/W
2
R/W
1
R
Description
Switching the
zone
IU
communication, 1 → IU
communication
0 → No error, 1 → IU
IU errors
Digital input
0 → Inactive, 1 → Active
Auxiliary heat
0 → Inactive, 1 → Active
Set-point
Localtemp
Room temperature
1 -→> Auto, 2 → Cooling,
Modes
3 → Heating, 4 →
Ventilation, 5 → Dry
0 → Automatic,
Speed
X → Position X [1-9] 10
Slats
Errors
Values
0 → Off, 1 → On
0 → No
ready
with error
Set-point
1 → Speed 1,
2 → Speed 2,
3 → Speed 3
- Swing
IU error codes
7
EN