Ionization Current; Firing Head Disassembly - Ecoflam BLU 18000.1 PR Manual Del Usuario

Quemador de gas progresivos
Ocultar thumbs Ver también para BLU 18000.1 PR:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 26
420010310700 BLU 15000.1 - 20000.1 PR TS
EN
The ionization current is checked by inserting a
microammeter with an end of scale of 50 µA (d.c.)
in series with the ionization probe.
A faulty position of the electrode can lead to a
reduction in the ionization current and cause a
safety cut-out of the burner due to a flame detec-
tion failure. In this case, check the position of the
electrode, its electric connection and the earthing
of the burner. The ionization current is normally > 20 µA.
REMOVING THE BLAST TUBE

IONIZATION CURRENT

16
min. 6 A
Microammeter
Microamperometro
fondo scala 50 A
50 μA end of scale
FIRING HEAD
DISASSEMBLY
24
LANDIS LFL1.622
LANDIS LFL1.333

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Blu 15000.1 prBlu 18000.1 tsBlu 15000.1 ts

Tabla de contenido